LIGHTNING . CONDUCTOR, or LIGHTNING ROD (Franklin), the name usually given to apparatus designed to protect buildings or ships from the destructive effects of lightning (Fr. paratonnerre, Ger. Blitzableiter). The upper regions of the atmosphere being at a different electrical potential from the earth, the thick dense clouds which are the usual prelude to a thunder storm serve to conduct the electricity of the upper air down towards the earth, and an electrical discharge takes place across the air space when the pressure is sufficient. Lightning discharges were distinguished by Sir Oliver Lodge
II Testing meters. 8 1.24 Type o Lamp . Number Distance Total Average c.p. Cost per c.p. of Lamps. apart (yds.) Cost. per Mile. per annum. Incandescent gas . 2,137 8o 7,062 839 i5.86d. Incandescent electric 90 66 288 1,373 13'71 Electric arcs 428 65 7,212 10,537 11.32 from the latter to earth takes such an erratic course that according to the Lightning Research Committee " no series of lightning conductors of the hitherto recognized type suffice to protect the building." In Germany two kinds of lightning stroke have been recognized, one as " ziindenden " (causing fire), analogous to the B flash, the other as " kalten " (not causing fire), the ordinary A discharge. The destructive effect of the former was noticed in 1884 by A. Parnell, who quoted instances of damage due to mechanical force, which he stated in many cases took place in a more or less upward direction.The object of erecting a number of pointed rods to form a lightning conductor is to produce a glow or brush discharge and thus neutralize or relieve the tension of the thunder-cloud. This, if the latter is of the A type, can be successfully accomplished, but sometimes the lightning flash takes place so suddenly that it cannot be prevented, however great the number of points provided, there being such a store
Protected Area.According to Lodge
wake
Material for Conductors.Franklin's original
sharp
Causes of Failure.A number of failures of conductors were noticed in the 1905 report of the Lightning Research Committee. One cause was the insufficient number of conductors and earth connexions; another was the absence of any system for connecting the metallic portion of the buildings to the conductors. In some cases the main stroke was received, but damage occurred by side-flash to isolated parts of the roof. There were several examples of large metallic surfaces being charged with electricity, the greater part of which was safely discharged, but enough followed unauthorized paths, such as a speaking-tube or electric bell wires, to cause damage. In one instance a flash struck the building at two points simultaneously; one portion followed the conductor, but the other went to earth jumping from a small finial to a greenhouse 30 ft. below. Construction of Conductors.The general conclusions of the Lightning Research Committee agree with the independent reports of similar investigators in Germany, Hungary and Holland. The following is a summary of the suggestions made: The conductors may be of copper, or of soft iron protected bygalvanizing or coated with lead. A number of paths to earth must be provided; well-jointed rain-water pipes may be utilized. Every chimney stack or other prominence should have an air terminal. Conductors should run in the most direct manner from air to earth, and be kept away from the walls by holdfasts (fig. 1), in the manner shown by A (fig. 2); the usual method is seen in B (fig. 2), where the tape follows the contour of the building and causes side flash. A building with a long roof should also be fitted with a horizontal
ridge
Earth Connexion.A copper plate not less than 3 sq. ft. in area may be used as an earth connexion if buried in permanently damp
being made to the nearest rain-water pipe to secure the necessary moisture. No further attention is required. Plate earths should be tested every year. The number of earths depends on the area of the building, but at least two should be provided. Insulators on the conductor are of no advantage, and it is useless to gild or otherwise protect the points of the air-terminals. As heated air offers a good path for lightning (which is the reason why the kitchen-chimney is often selected by the discharge), a number of points should be fixed to high chimneys and there should be at least two conductors to earth. All roof metals, such as finials, flashings, rain-water gutters, ventilating pipes, cowls and stove pipes, should be connected to the system of conductors. The efficiency of the installation depends on the interconnexion of all metallic parts, also on the quality of the earth connexions. In the case ; Q,;'i a .qor of magazines used for explosives, it is .: questionable whether the usual plan of FIG. 5.Tubular Earth. erecting rods at the sides of the buildings is efficient. The only way to ensure safety is to enclose the magazine in iron; the on Roof. next best is to arrange the conductors so that they surround it like a bird cage. End of Article: LIGHTNING If you wish, you can link directly to this article.